Page 342 - Practical Power System and Protective Relays Commissioning
P. 342

Protective Relays Testing and Commissioning Chapter | 20  337
















             FIGURE 20.3.4 SOTF Logic in distance protection.

                Simulate the CB being switched off by binary input from CB auxiliary
             contact for more than 110 seconds.
                A close command is given during this time, then SOTF is enabled for
             500 ms. During this time if the measured current is more than 2 A then
             the SOTF OC relay will operate and bypass the operation of distance relay
             element. Refer to SOTF Logic in Fig. 20.3.4.
             8. Fuse failure blocking function
                   If a symmetrical zero-sequence voltage 3V 0 is detected and a symmet-
                rical zero-sequence current 3I 0 is detected, then the fuse failure function
                will operate after 5 seconds, during this time if unsymmetrical 3I 0 is
                detected the relay will reset the fuse failure blocking of the distance relay
                as there is a real fault on the system. Some manufacturers also switch on
                to instantaneous OC relay protection during blocking of distance protec-
                tion by the fuse failure function.
                   Also, distance protection is blocked when the Minature Circuit
                Breaker (MCB) of the VT secondary circuits are tripped due to a fault on
                the VT secondary. This is provided to the distance protection as binary
                inputs from MCB’s auxiliary contacts.
             9. Directional load tests
                After energizing the line and the phasing test check is completed then
             this test is carried out on at least 10% 25% of normal load current of the
             circuit. The normal load circuits are resistive or resistive-inductive loads.
             The load will be in phase or lagging of the voltage.
                When CT’s earthing of the star point is in the line side direction for the
             above inductive resistive load the direction of distance measurement should
             be in first quarter as shown in Fig. 20.3.5.
                The values of MW, MVAR, voltage, and current phase angle are tested if
             the direction of the load is as per Fig. 20.3.5. The direction of distance
             protection measurement is correct, otherwise check that the setting on the
             distance protection in the line side for CT’s star point if the direction is not
             correct then we should switch off the circuit to modify the CT star point
   337   338   339   340   341   342   343   344   345   346   347