340  Practical Power System and Protective Relays Commissioning































            FIGURE 20.4.2 Pilot wire line differential protection for AC and DC circuits.




              TABLE 20.4.1 Test Sheet 1
              Injected     Relay Operation Current  Relay Operation Current
              Phase        End A                    End B
              R N
              Y N
              B N
              R Y
              Y B
              B R



            operates. Repeat this test for the other two phases, then repeat the test for
            phase phase injection and measure the value at which the relay will operate,
            as shown in Fig. 20.4.2 and Table 20.4.1.
               Repeat the above test, but put back the trip links and check the value of
            the current at which the relay will trip at one phase at least, and check the
            same at the other end of the line.