Page 348 - Practical Power System and Protective Relays Commissioning
P. 348

Protective Relays Testing and Commissioning Chapter | 20  343























             FIGURE 20.4.6 Biased differential protection characteristic for transmission lines.

















             FIGURE 20.4.7 Test of relay bias characteristic.


                A drawing of the relay characteristic should follow the relay characteris-
             tic provided by the manufacturer.
                1.4 Differential relay operating time
                Connect the relay and secondary injection tester as shown in Fig. 20.4.8.
                Inject current of more than 0.2 A and check the operating time of the
             relay repeat. This test is used for all phase-N and pH pH injection.
             Complete a table with the results.
                1.5 On-load test
                When the line is energized and loaded, measure the differential current,
             bias current for each phase on both ends of the line directly on the relay on
             the MHI. Then reverse the CT connection star point from the line side to the
             busbar side and check the value of the differential current which should be
             raised. This test should be done with all tripping links of the relays at both
             sides of the line opened.
   343   344   345   346   347   348   349   350   351   352   353