Page 352 - Practical Power System and Protective Relays Commissioning
P. 352

Protective Relays Testing and Commissioning Chapter | 20  347



               TABLE 20.5.2 Test Sheet 1
               Injected   Injected     Calculated Trip  Measured Trip  Error
               Phase      Current      Time            Time           %
               R          1.5 I diff
               Y
               B



























             FIGURE 20.5.3 Power transformer with shorting between the HV side and LV side bushings to
             bypass the transformer impedance. As shown in Figs. 20.5.4 and 20.5.5 an external fault is simulated.

             2. When the transformer is overfluxing then it absorbs high current from one
                side of the transformer, which can lead to a false trip. This current of overex-
                citation is rich in fifth harmonic, which is not the case for the fault current.
                Normally I second harmonic set 5 15% I diff and I fifth harmonic set 5 30% I diff .
                Inject the relay with the second harmonic up to 15% Idiff then check that
             the relay will be blocked above this value, also, check that the relay will
             blocked above 30% I diff for the fifth harmonic.


             20.5.3 PRIMARY INJECTION TEST

             In this test we do a stability test by supplying the transformer HV side with
             380 V and SC the power transformer at the LV side, if the current is not
             enough we can SC the power transformer winding between the HV bushing
             and LV winding, as shown in Figs. 20.5.3 and 20.5.4.
   347   348   349   350   351   352   353   354   355   356   357