Page 355 - Practical Power System and Protective Relays Commissioning
P. 355

350  Practical Power System and Protective Relays Commissioning


            Subchapter 20.6


            Busbar Protection Testing and
            Commissioning


            20.6.1 SECONDARY INJECTION TEST FOR THE
            DISCRIMINATING ZONE

            The most used scheme is a high-impedance differential protection.
            1. Pickup test of busbar protection modules
                  Put the busbar protection out of service during this test—this means
               the buswires will be short-circuited and trip links will be opened.
                  Inject the current to each module of the busbar protection to check
               the pickup value, which should be 6 5% of the normal pickup setting of
               the relay.
            2. Pickup test of the breaker failure module if it is attached to the Busbar
               protection system
                  Inject this module with current and check the pickup value is within
               6 5% of the nominal pickup value. This is done after opening the trip
               link of the Breaker Failure (BF) system of the substation.
            3. Time test measurement of BF relay
                  Simulate a BF initiation signal and inject a current above the relay
               setting, then allow BF time and check the operation of the BF trip—
               normally it is set to 125 ms. Check that the measured time is 6 5% of
               the time set on the relay.
            4. Busbar isolator image test (refer to Fig. 20.6.1).























            FIGURE 20.6.1 Busbar discrimination test of fault location.
   350   351   352   353   354   355   356   357   358   359   360