Page 351 - Practical Power System and Protective Relays Commissioning
P. 351

346  Practical Power System and Protective Relays Commissioning
























            FIGURE 20.5.2 Differential relay characteristic.


              TABLE 20.5.1 Test Sheet 1

              Injected  Injected  I bias  I bias   I diff    I diff    Error
              Current  Current  Calculated  Measured  Calculated  Measured  %
              HV Side  LV Side

              I R      I r
              I Y      I Y
              I B      I b
              HV, high voltage; LV, low voltage.


               Then Table 20.5.1 should be completed and the two values measured and
            calculated should be compared to check the relay characteristic operation.
            3. Trip time test
                  By injecting the relay with about 1.5 I diff , the trip time for each phase
               can be measured (injection will be done from the HV side only as this is
               sufficient). Then Table 20.5.2 is completed with the measured values.
            4. Harmonic restrain test

               As we know from previous chapters of this book, the differential relay of
            the transformer will be blocked in two cases as follows:
            1. In the case of a high-value inrush current during energization of the
               transformer this current can be distinguished from the fault current by the
               second harmonic current as the inrush current is rich in this harmonic but
               does not exist in the fault current.
   346   347   348   349   350   351   352   353   354   355   356