Page 360 - Practical Power System and Protective Relays Commissioning
P. 360

Protective Relays Testing and Commissioning Chapter | 20  355


                   The tests in Sections 20.6.1 and 20.6.2 are repeated for the check
                zone if a separate CT is provided for this check zone.
             5. CT supervision test
                This unit is overcurrent relay and is set to monitor the differential circuit
             for each phase and to give an alarm after a time delay of about 3 seconds
             when one CT secondary circuit is detected as open and to switch off that
             zone of the busbar protection. This can be tested by injecting a current
             greater than the required setting for 3 seconds then checking the operation of
             the relay to SC the buswires which this CT is connected to and putting this
             faulty zone of the CT out of service.



             Subchapter 20.7


             Synchronizing Relay Testing and

             Commissioning

             20.7.1 INTRODUCTION

             When there are two parts of a power system network, each has a separate
             generation to be connected together. This connection should avoid any
             damage to the power system components or shock loads.
                The voltage, phase angle, and frequency difference between the two
             connected systems should be within the acceptable limits. There are two
             methods for synchronizing:
             1. Check synchronizing
                   When the two systems are tied by an open breaker then the two
                frequencies will be different and the phase angle difference will increase
                (slow slip).
             2. System synchronizing

                When the two systems are asynchronous, as two generation islands, the
             rate of slip between the two frequencies will be high. Then the system
             synchronizing limits are applied. In this case, the phase angle limit will be
             narrow and closure of the CB will be allowed when the phase angle differ-
             ence decreases.
                Refer to Fig. 20.7.1 to check the synchronizing and system check
             operation.
                Check synchronizing limits:
                ΔF 5 50 mHz
                ɸ 5 35-60 degrees
   355   356   357   358   359   360   361   362   363   364   365