360  Practical Power System and Protective Relays Commissioning


               However, when impedance passes from zone A to zone B only or from
            zone C to zone B only, this is considered as an external faults and no trip
            will occur.


            20.8.2 RELAY CONNECTION

            Refer to the following (Fig. 20.8.2), for out-of-step relay test connections































            FIGURE 20.8.2 Out-of-step relay test connections.

            20.8.3 TEST PROCEDURE
            By injecting a fixed current of 1 or 2 A then the value of the injected voltage
            is changed to simulate the following conditions and the relay response is
            checked as follows:
               Impedance passes from Z A -Z B -Z C -trip;
               Impedance passes from Z C -Z B -Z A -trip;
               Impedance passes from Z A -Z B -no trip;
               Impedance passes from Z C -Z B -no trip.