Page 362 - Practical Power System and Protective Relays Commissioning
P. 362

Protective Relays Testing and Commissioning Chapter | 20  357


             20.7.2 SYNCHRONIZING RELAY TEST
             A relay connection is shown in Fig 20.7.2, where:
                V 1 5 running voltage;
                V 2 5 incoming voltage.
                The settings are:
                ΔF 5 20 mHZ Δ ɸ 5 30 degrees
                ΔV 5 10% blocking voltage 5 45% V n
                Live line 5 55% V n dead line 5 25% V n
                Live bus 5 55% V n dead bus 5 25% V n
                Connect the circuit as shown in Fig. 20.7.2 then perform the following tests.

             1. Differential voltage pickup test
                   Inject a fixed voltage of  110  5 63.5 V as the running voltage with a
                                        O3
                fixed angle of 5 degrees between the two voltages. Then inject the incom-
                ing voltage with the relay set for ΔV 5 5% and check the pickup value for
                the running voltage and pickup value of the incoming voltage. Repeat the
                last steps for ΔV 5 7.5% and ΔV 5 10% and complete Table 20.7.1.
             2. Differential angular pickup test
                   Inject the running voltage (bus voltage) and incoming voltage (line
                voltage) at different phase angles, then check the pickup value of the
                phase angle as shown in Table 20.7.2. This will be at fixed F, which
                means ΔF 5 0.
             3. Differential frequency pickup
                   Inject V 1 and V 2 at fixed Δɸ 5 10 degrees, then check the
                ΔF 5 20 mHZ setting and complete Table 20.7.3.

























             FIGURE 20.7.2 Synchronous relay test connections.
   357   358   359   360   361   362   363   364   365   366   367