Chapter 21





             A Guided Practical Value of


             Some Test Results Collected
             From Actual Power System


             Testing at Site




             21.1 POWER TRANSFORMER TEST
             Example 1:
                75/75/25 MVA transformer
                220/70/11.5 kV F 5 50 Hz
                1. Insulation resistance of winding
                Injected voltage 5 5kV DC
                High voltage (HV)—E 1250 MΩ
                Low voltage (LV)—E 3000 MΩ
                HV—LV 4000 MΩ
                Tertiary—E 3000 MΩ
                HV—tertiary 5000 MΩ
                LV—tertiary 3500 MΩ
                2. Wiring insulation
                Injected voltage 5 1000 V
                R . 1000 MΩ
                3. Fan motor consumption
                I N 5 1.8 Amp
                I Start 5 7.62 Amp
                Example 2:
                125/125/45 MVA
                220/70/11.5 kV
                1. Audio noise level test
                Average level of noise 5 77 dB








             Practical Power System and Protective Relays Commissioning.