Page 363 - Practical Power System and Protective Relays Commissioning
P. 363

358  Practical Power System and Protective Relays Commissioning



              TABLE 20.7.1 Differential Voltage Pickup Test
              ΔV%     φ (degrees)  Running    Incoming      V 1     V 2
              Set                Voltage V 1  Voltage V 2   Pickup  Pickup
              5%      5          63.5         63.5
              7.5%    5          63.5         63.5
              10%     5          63.5         63.5





              TABLE 20.7.2 Differential Angular Pickup Test

              Δφ Set (degrees)  V Line V 2  V Bus V 2  Phase Angle Pickup
                                                       Lead Side   Lag Side
              10                63.5        63.5
              20                63.5        63.5
              30                63.5        63.5




              TABLE 20.7.3 Differential Frequency Pickup Test

              ΔF Set       V 1       V 2        Δφ (degrees)      ΔF Pickup
              20 mH        63.5      63.5       10




            4. Blocking voltage test
                  Reduce the bus voltage and line voltage to 45% of V n -28.575 V.
               Then check that the relay will block operation at this level of voltage and
               below, and that it will operate above this voltage.
            5. Check the live and dead voltage monitor for bus and line voltage
               This feature monitors the running and incoming voltage and considers the
            line live for voltages above 55% V n and considers the line dead for voltages
            less than 25 %V n . The same applies for the bus voltage monitor. This feature
            allows bypassing of the synchronizing operation for dead conditions of the
            line or bus.