Page 368 - Practical Power System and Protective Relays Commissioning
P. 368

A Guided Practical Value of Some Test Results Chapter | 21  363


                6. Dielectric tests
                HV test at power cycle 50 c/s
                HV—E-230 kV
                LV—E-70 kV
                Tertiary—E-28 kV
                For 1 minute
                7. AC 31.2 kV at tertiary winding at 200 C/S test
                For 30 seconds
                Tertiary wilding-31.2 kV at 200 C/S
                Then measure HV—E-460 kV at 200 C/S
                Voltage per turn, 2.68 times the rated value.

             21.2 HIGH-VOLTAGE TRANSMISSION LINE IMPEDANCE
             VALUES
             220 kV line
                Bundle aluminum
                R 1 5 0.14 Ω/km
                X 1 5 0.4 Ω/km
                X 0 5 2.04 Ω/km

             21.3 GAS INSULATED SYSTEM TESTS
             Disconnecting switch: contact resistance 5 10 μΩ
                Earthing network resistance 5 10 μΩ
                Gas insulated system (GIS) main circuit resistance 66 kV between 2 bays
             with 100 Amp DC injected
                R 5 160 280 μΩ
                Circuit breaker operating time
                T close 5 55 ms
                T open 5 33 ms
                Disconnecting switches
                T open , 2 seconds
                T close , 3 seconds
                High-speed earthing switches
                T open , 18 seconds
                T close , 18 seconds
                High-voltage test for GIS
                Example:
                For 132 kV GIS we apply 235 kV for 1 minute.
                For 22 kV SWG we apply 50 kV for 1 minute.

             21.4 LOW VOLTAGE PANELS
             Torque wrench key 5 70 nm.