368  Practical Power System and Protective Relays Commissioning


               polarity on one side of the power transformer CTs. The secondary relay
               will pickup as the differential current is increased, with the relay before
               the test isolated from the tripping circuit, then the current polarity of the
               CTs is restored.
            2. Busbar differential protection
               With the trip contacts of busbar protection are isolated we can measure
            the differential current on the relay by shorting the CT input of each feeder
            connected to the specified zone of protection. We should have a rise in dif-
            ferential current and the relay should issue a trip signal to the bus zone
            which this feeder is connected to.