Page 357 - Practical Power System and Protective Relays Commissioning
P. 357

352  Practical Power System and Protective Relays Commissioning


            2. Phasing of the reference circuit CT
               As in the ratio test we choose F1 (feeder 1) as a reference circuit, then
            we check the correct polarity of the reference feeder CTs by injecting a
            current through a primary test set through two phases, as shown in
            Fig. 20.6.3.
               The correct polarity of the reference circuit CT connection exists when
            the reading of I 2 in the neutral circuit of CTs is near zero, otherwise the
            polarity will not be correct and we must review the CT connection and star
            point connection of the CTs. This test is done with temporary SC of R, Y,
            and B phases, as shown in Fig. 20.6.3.
               Repeat the above test between phases Y and B, then between phases B
            and R. All should read a few milli-Amperes or near zero for the correct
            polarity of the CT connection on feeder F1.
               Now we have a reference circuit F1 checked for ratio and polarity, then
            we check other circuit CTs by injecting a primary current between the refer-
            ence circuit and other circuits one by one as F2, as shown in Fig. 20.6.4.
               Then, by comparing I 2 and I 4 for a ratio check and I 3 and I 5 for a polarity
            check, the test between the reference circuit F1 and other feeders F3 and F4
            is repeated.


































            FIGURE 20.6.3 Polarity check for reference circuit F1.
   352   353   354   355   356   357   358   359   360   361   362