Page 68 - Practical Power System and Protective Relays Commissioning
P. 68

Power Transformers Theory Testing and Commissioning Chapter | 5  65















             FIGURE 5.19 (A) The object under test, (B) The equivalent circuit of the object under test,
             (C) The vector Diagram.


               TABLE 5.3 Temperature Difference Coefficient C

               Temperature  1  2     3    4    5    10   15   20   25   30
               Difference
               Coefficient C  1.03  1.06  1.09  1.12  1.15  1.31  1.51  1.75  2.00  2.3



             (the pores, impurities, and humidity that cause the ionization in the insulation
             material).
                The power factor measurement of the insulation at certain frequency
             gives basic information regarding the insulation. The measurements to be
             made during the service are one of the most important indications, indicating
             the age of the insulation and the contamination of the oil. The active losses
             of the circuit are calculated as follows
                                P 5 VUIUcos φ 5 VUCUωUtanδ
                Capacitance, tan δ, active losses, and cos φ can be measured by bridge
             methods or a power factor (cos φ) measuring instrument at definite voltages.
                Measurement is performed between the windings and the tank, and the
             test temperature is recorded; then according to desired reference value the
             necessary corrections are undertaken. Most test devices use 10 kV as a test
             voltage but there is a correction factor C to refer the reading to the tempera-
             ture measured at factory as per Table 5.3.
                tan δ1 should be measured at the factory, and tan δ2 measured at site,
             and the calculation is:

                            Difference DðÞ 5 tan δ1 2 tan δ2
                                                       3 100
                                       tan δ1
                Difference (D) should be less than 30% and less than 15% in overhaul
             maintenance. Refer to Fig. 5.20 for the equivalent circuit of the electrical
             insulation of two winding transformers.
   63   64   65   66   67   68   69   70   71   72   73