Page 64 - Practical Power System and Protective Relays Commissioning
P. 64

Power Transformers Theory Testing and Commissioning Chapter | 5  61












             FIGURE 5.15 Voltage ratio test of power transformer.

























             FIGURE 5.16 Vector group test of power transformer.

             power supply of 380 V from the high voltage side and measuring the vol-
             tages between Y y, B y, B b, and Y b. These voltage vectors are then
             drawn, noting that the voltages R and r should coincide as they are at the
             same potential and phase displacement as there is a jumper between R and r.
             An example vector diagram is shown in Fig. 5.16.
                Then next step is to transfer the vector diagram to the clock remembering
             that the phase Y are on the 0 degree or 12 o’clock position. We find that the
             voltage (y) is lagging the voltage (Y) by 150 degrees (5 multiplied by 30
             degrees) and the vector group is nominated as (Yd5). After the test is com-
             plete, the transformer winding should be earthed to ensure that it is
             discharged.


             5.6.4 Winding Resistance Test
             In a winding resistance test we use a voltmeter and an ampere meter (also
             known as an ammeter) and a battery of 12 or 24 V. For low-resistance values
             we connect the voltmeter after the ammeter, but in high-resistance values we
   59   60   61   62   63   64   65   66   67   68   69