Power Transformers Theory Testing and Commissioning Chapter | 5  59


             5.6 POWER TRANSFORMER TESTING AND
             COMMISSIONING

             5.6.1 Measurement of Winding Insulation Resistance
             In this test we use a Megger tester for insulation measurements 5 kV for
             1 minute; if the reading is not stable then we should extend the test for
             5 minutes.
                As a reference guide, when testing a 66/11 kV star/delta power trans-
             former the following results were derived:

                3 phases 66 kV winding to earth is 5000 MΩ.
                3 phases 11 kV winding to earth is 1000 MΩ.
                3 phases 66 kV winding to 11 kV winding is 1500 MΩ.

                Refer to Fig. 5.14.
                The insulation resistance measured for 1 minute is called R 60 . It is also
             measured for 15 seconds at the site temperature. These two calculations
             should be compared to the factory temperature as shown in Table 5.2.
                The calculation should be:
                R 60 measured at factory 5 K 3 R 60 measured at site
                                           R 60 measured 2 R 60 at factory
                       Insulation difference 5
                                                 R 60 at factory
                                           3 100 should be less 30%
                This percentage for overhaul maintenance should not exceed 15%.



























             FIGURE 5.14 Measurement of power transformer winding insulation resistance.