Page 65 - Practical Power System and Protective Relays Commissioning
P. 65

62  Practical Power System and Protective Relays Commissioning


            connect the voltmeter before the ammeter. A heavy current of 100 A and
            sensitive meters should give good results.
               During the test we connect the voltmeter after the current reaches the sat-
            uration point and we disconnect voltmeter before disconnecting the ammeter.
            To reduce the time needed for the current to reach saturation condition, we
            connect a variable resistance in series with the circuit.
               The resistance reading at site should be compared to the resistance tem-
            perature reading at factory by using this equation:

                                        ð T 2 1 235Þ 3 R 1
                                   R 2 5
                                          ðT 1 1 235Þ
               where R 1 is the Resistance reading at factory, T 1 is the Temperature
            which reading is taken at factory, R 2 is the Resistance reading at site, T 2 is
            the Temperature which reading is taken at site.
               The measurement difference, D, calculated by
                                  D 5 R 2   R 1 Þ=R 1 3 100
                                      ð
               should not exceed 2%.
               If the resistance measurement is very low, there is a possibility of short
            circuits in the transformer windings.
               If the resistance measurement is low, then there is a possibility of bad
            contacts between the winding and insulators, or bad contact in the tap
            changer, or the winding may be damaged.

            5.6.5 Measurement of No-Load Current and No-Load Circuit
            Losses Test
            Under open-circuited conditions on a transformer’s high voltage side, the
            transformer no-load current (magnetizing current) is less than 4% of full
            load current. Any power losses in this condition is the loss of iron which
            includes hysteresis losses and eddy current losses. The test is done as shown
            in Fig. 5.17.
               P 0 5 Measured no-load power losses
               No-load current losses I 0 5 A—ammeter reading in each phase.
               These losses affect the power transformer efficiency.

            5.6.6 Measurement of Load Losses: Current and Impedance
            Voltage Test
            Short-circuit (load) losses and short-circuit impedance voltage are guaranteed
            and reported values by the manufacturer to customers. Short-circuit imped-
            ance voltage is an important parameter especially for the parallel operation
            of the transformers, whereas short-circuit losses are important from economi-
            cal point of view as they effect the transformer efficiency.
   60   61   62   63   64   65   66   67   68   69   70