Page 214 - Reciprocating Compressors Operation Maintenance
P. 214

2OO    Reciprocating Compressors: Operation and Maintenance


         starter  circuit. This  allows the  unit  to  unload for  only a  few  seconds  of
         starting, or long enough for the motor to attain full  speed.

         DUAL  CONTROL


           Sometimes, the conditions of service within a plant favor  both types of
         control, bypass  and start-stop.  For  instance,  the air requirements  may be
         reduced  to only a small fraction of  the compressor  capacity  on Saturday
         and  Sunday.  Plant-specific  conditions  obviously  call  for  a  combination
         control  employing  the  best  elements  of  the  two  previously mentioned
         control types, bypass and start-stop.


         Three-Step Variable  Control

           This control, which uses suction valve unloading, regulates  capacity in
         steps  of  100%, 50% and 0% of full  capacity  and is activated  by some  sort
         of governor. The actual unloading of the compressor  can take place  elec-
         trically and pneumatically, or pneumatically  only.
           Figure  3-55  shows  a  pneumatic control  panel  including controls  for
         electric  auxiliaries. Included  are  switches  and  pressure  gauges  for  indi-
         cating the intercooler and system and oil pressures.
           Normally, for a  100 psig air system, the pressure  switches  would be set
         to completely  unload at  100 psig. When the pressure  falls  to 95 psig,  the
         compressor  would  load  to 50% capacity, and  if the pressure  continues to
         fall  to 93 psig, the compressor  would be completely  loaded.
           Rising pressure would cause the compressor to unload to 50% capacity
         at  98  pisg  and  completely  unload  for  automatic  initial  unloading.  Thus,
         whenever  the  compressor  is  started,  it  will  always start  unloaded.  It  is
         also unloaded when stopped.
           Figure  3-56  shows  diagrammatically  the  sequence  of  operation  of
         unloading with the three-step control.

         CLEARANCE   CONTROL


           Although  bypass control  constitutes the  major portion  of  the  capacity
         control devices,  other methods are available  and are often used. There  are
         many  instances when bypass  control  does  not  offer  the  necessary  flexi-
         bility for a given control application.
   209   210   211   212   213   214   215   216   217   218   219