Page 123 - Shale Shakers Drilling Fluid Systems
P. 123

106   SHALE SHAKERS AND DRILLING FLUID SYSTEMS



        The rig power supply should provide constant            For example, a shale shaker is designed to op-
        voltage and frequency to all electrical components    erate at 4 G's and has an angular displacement,
        on the rig. Most drilling rigs generate 460 VAC,      or stroke, of 0.09 inch. This shaker must vibrate
        60 Hz, 3-phase power or 380 VAC, 50 Hz, 3-phase       at 1750 rpm to produce 4.1 G's. At 60 Hz, the
        power. Other common voltages include 230 VAC,         motor turns at 1750 rpm, which yields a "G"-
        190 VAC, and 575 VAC. Through transformers and        factor of 4.1, just as designed. If the frequency drops
        other controls, a single power source can supply      to 55 Hz, the motor speed reduces to 1650 rpm,
        a variety of electrical power to accommodate the      resulting in a "G"-factor of 3.5. Further reduction
        requirements of different rig components.             of frequency to 50 Hz results in 1500 rpm and a
          Shale shakers should be provided with motors        "G"-factor of 2.9.
        and starters that match the rig generator output.       Most rigs provide 460 VAC, 60 Hz power and
        Most motors are dual-wound. These may be wired        most shale shakers are designed to operate with
        to accommodate two voltages and starter configu-      this power supply. However, many drilling rigs are
        rations. For example, some dual-wind motors op-       designed for 380 VAC, 50 Hz electrical systems. To
        erate at 230/460 VAC, while others operate at         provide proper "G"-factors for 50 Hz operations,
        190/380 VAC. Dual-wind motors allow the shaker        shale shaker manufacturers rely on two methods:
        to operate properly with either power supply af-      increasing stroke length or through the use of
        ter relatively simple rewiring. Care must be taken,   voltage/frequency inverters (transformers).
        however, to make certain that the proper voltage        A motor designed for 50 Hz applications rotates
        is used. Additionally, electrical motors are de-      at 1500 rpm. At 0.09 inch stroke a shale shaker
        signed to rotate with a specific speed. Typically the  will produce 2.9 G's. Increasing the stroke length
        rotational speed is 1800 rpm for 60 Hz applications   to 0.13 inch provides 4.1 G's, similar to the ori-
        and 1500 rpm for 50 Hz applications.                  ginal 60 Hz design. However, the longer stroke
          Shale shakers use a vibrating screen surface to     length and slower speed will produce different
        conserve the drilling fluid and reject drilled solids.  solids separation and conveyance performance. At
        The effects of this vibration are described in terms  the longer stroke lengths, shakers will probably
        of the "G"-factor, or the function of the angular     convey more solids and have a higher fluid capac-
        displacement of a screen surface and the square       ity. If the stroke length is not increased, some
        of the rotational speed. Angular displacement is      manufacturers use voltage inverters to provide
        achieved by rotating an eccentric mass. Most shale    460 VAC, 60 Hz output power from a 380 VAC,
        shakers are designed to be operated at a specific,    50 Hz supply.
        fixed "G"-factor by matching the stroke to a given      Constant electrical power is necessary for proper,
        machine rotational speed. It follows that any         consistent shale shaker performance. Tables 3-2
        deviation in speed will affect the "G"-factor and in-  and 3-3 below assist in designing a satisfactory
        fluence performance.                                  electrical distribution system. Alternating current
          Deviations in speed may be caused by one or         (AC) motors are common on most shale shakers.
        more factors. Typically, they are caused by fluctua-  The motor rating indicates the amount of electri-
        tions in voltage or the frequency of the alternat-    cal current required to operate the motor. The
        ing current. If the voltage drops, the motor can-     values in Table 3-2 provide some guidelines for
        not produce the rated horsepower and may not be       various motors. The manufacturer's recommenda-
        able to sustain the velocity needed to keep the       tion should always take precedence over the gen-
        eccentric mass moving properly. Low voltage also      eralized values in these tables. The amount of
                                                                                            f
        reduces the life of electrical components. Devia-     electric current that a conduc  ^r wire) can
        tions in frequency result in the motor turning        carry increases as the diameter of the wire in-
        faster (frequencies higher than normal) or slower     creases. Common approximate values for currents
        (frequencies lower than normal). This directly in-    are presented with the corresponding wire size
        fluences rpm and shaker performance.                  designation in Table 3-3. Conductors, or even rela-
          Slower rpm reduces the "G"-factor, causes poor      tively large-diameter wire, still have some resis-
        separation, and poor conveyance. Faster rpm in-       tance to the flow of electric current. This resis-
        creases the "G"-factor and, although it may im-       tance results in a line voltage drop. When an
        prove conveyance and separation, often increases      electric motor is located in a remote area relative
        screen fatigue failures. In extreme cases, higher     to the generator, the line voltage drop may de-
        rpm may cause structural damage to the shaker.        crease the motor voltage to unacceptably low val-
        Thus, it is important to provide proper power to      ues. Wire diameter guidelines necessary to maintain
        the shale shaker.                                     the voltage drop to 3% are presented in Table 3-4.
   118   119   120   121   122   123   124   125   126   127   128