Page 285 - The Engineering Guide to LEED-New Construction Sustainable Construction for Engineers
P. 285

248    Cha pte r  S i x
































             FIGURE 6.0.2  This does not meet IEQ Prerequisite 1 for natural ventilation. Hatched area is not
             within 25 ft of operable windows.

             IEQ Prerequisite 2: Environmental Tobacco Smoke (ETS) Control
             The purpose of this prerequisite is to prevent secondhand smoke from going into areas
             other than designated or desired smoking areas of buildings.

             USGBC Rating System
             LEED-NC 2.2 lists the Intent, Requirements, and Potential Technologies and Strategies
             for IEQp2 as follows, with modifications as noted to update to LEED 2009:

                Intent
                Prevent or minimize exposure of building occupants, indoor surfaces, and ventilation air
                distribution systems to Environmental Tobacco Smoke (ETS).
                Requirements
                Case 1. All Projects (As per LEED 2009)
                OPTION 1
                  •  Prohibit smoking in the building.
                  •  Locate any exterior designated smoking areas at least 25 feet away from entries,
                    outdoor air intakes and operable windows. (LEED 2009 requires signage to allow
                    smoking and/or prohibit smoking in designated areas, or prohibit smoking totally.)
                OR
                OPTION 2
                  •  Prohibit smoking in the building except in designated smoking areas.
                  •  Locate any exterior designated smoking areas at least 25 feet away from entries,
                    outdoor air intakes and operable windows. (LEED 2009 requires signage to allow
                    smoking and/or prohibit smoking in designated areas, or prohibit smoking totally.)