Page 287 - The Engineering Guide to LEED-New Construction Sustainable Construction for Engineers
P. 287

250    Cha pte r  S i x


             to smoke, then these areas are adequately segregated by a combination of physical barriers
             and negative pressure so that the contaminants from tobacco smoke do not enter the other
             areas. There is also the potential for secondhand smoke to enter a facility if smoking is
             allowed near openings to the outdoors and air intakes. Therefore, if outdoor smoking areas
             are allowed on a site, they must be located away from these potential avenues for indoor
             contamination. The requirements listed previously in the USGBC LEED-NC 2.2 and 2009
             rating system sections give very good explanations of what is required. Project teams should
             also make sure they abide by local and state smoking bans. A useful summary of the various
             options and requirements can be found in Fig. 6.0.3. Note the following unit conversions:
                                          1 atm ~ 101,300 Pa
                                         1 in of water ~ 249 Pa


                                                       Outdoor Source > 25 ft from
                                                       Openings with proper signage
                                        Option 1
                                       (Do Both)
                                                             No Smoking
                      All Projects
                     (Either Option)
                                                        Outdoor Source > 25 ft from
                                                       Openings with proper signage
                                        Option 2
                                                     Smoking in Designated Areas with
                                       (Do Both)
                                                     - Exhaust to Outdoors
                                                     - Impermeable Deck to Deck
                                                     - Negative Pressure and Test

                                                        Outdoor Source > 25 ft from
                                                       Openings with proper signage

                                                       No Smoking in Common Areas

                                                         Seal Penetrations/Chases

                                                      Common Hallways: Either
                                                      - Doors Weather-stripped
                      Residential                       or
                      (Do All Six)
                                                      - Hallway Pressurized and Tested
                                                      - Door Leak Test per ANSI/ASTM
                                                        E779-03 and
                                                      - Sampling per Chapter 4 Residential
                                                        Manual for Compliance with
                                                        California’s 2001 Energy Efficiency
                                                        Standards
                                                      Weatherstrip All Exterior Doors and
                                                        Operable Windows in the Units
             FIGURE 6.0.3  Summary of ETS requirements: all the listed items for each option must be
             followed for LEED 2009.
   282   283   284   285   286   287   288   289   290   291   292