LEED Indoor Envir onmental Quality     249

                  •  Locate designated smoking rooms to effectively contain, capture and remove ETS
                    from the building. At a minimum, the smoking room must be directly exhausted to
                    the outdoors (and as noted in LEED 2009 away from air intakes and building entry
                    paths) with no re-circulation of ETS-containing air to the non-smoking area of the
                    building, and enclosed with impermeable deck-to-deck partitions. With the doors to
                    the smoking room closed, operate exhaust sufficient to create a negative pressure
                    with respect to the adjacent spaces of at least an average of 5 Pa (0.02 inches of water
                    gauge) and with a minimum of 1 Pa (0.004 inches of water gauge).
                  •  Performance of the smoking room differential air pressures shall be verified by
                    conducting 15 minutes of measurement, with a minimum of one measurement every
                    10 seconds, of the differential pressure in the smoking room with respect to each
                    adjacent area and in each adjacent vertical chase with the doors to the smoking room
                    closed. The testing will be conducted with each space configured for worst case
                    conditions of transport of air from the smoking rooms to adjacent spaces with the
                    smoking rooms’ doors closed to the adjacent spaces.
                Case 2. Residential and Hospitality Projects Only (As per LEED 2009)
                (Listed in LEED 2.2 as OPTION 3-For residential buildings only)
                  •  Prohibit smoking in all common areas of the building.
                  •  Locate any exterior designated smoking areas (including balconies as per LEED 2009)
                    at least 25 feet away from entries, outdoor air intakes and operable windows opening
                    to common areas. (LEED 2009 requires signage to allow smoking and/or prohibit
                    smoking in designated areas, or prohibit smoking totally.)
                  •  Minimize uncontrolled pathways for ETS transfer between individual residential
                    units by sealing penetrations in walls, ceilings and floors in the residential units, and
                    by sealing vertical chases adjacent to the units.
                  •  All doors in the residential units leading to common hallways shall be weather-
                    stripped to minimize air leakage into the hallway. If the common hallways are
                    pressurized with respect to the residential units then doors in the residential units
                    leading to the common hallways need not be weather-stripped provided that the
                    positive differential pressure is demonstrated as in (Case 1) Option 2, considering the
                    residential unit as the smoking room.
                  •  Acceptable sealing of residential units shall be demonstrated by a blower door
                    test  conducted in accordance with ANSI/ASTM-E779-03, Standard Test Method for
                    Determining Air Leakage Rate By Fan Pressurization, AND use the progressive sampling
                    methodology defined in Chapter 4 (Compliance Through Quality Construction) of the
                    Residential Manual for Compliance with California’s 2001 Energy Efficiency Standards
                    (http://www.energy.ca.gov/title24/2001standards/residential_manual/index.html).
                    Residential units must demonstrate less than 1.25 square inches leakage area per
                    100 square feet of enclosure area (i.e., sum of all wall, ceiling and floor areas).
                  •  LEED 2009 also requires that all exterior doors and operable windows in the residential
                    units are weather stripped to minimize leakage from outdoors.

                Potential Technologies and Strategies
                Prohibit smoking in commercial buildings or effectively control the ventilation air in
                smoking rooms. For residential buildings, prohibit smoking in common areas, design
                building envelope and systems to minimize ETS transfer among dwelling units.
             Calculations and Considerations
             Either no smoking is allowed in a building, or if there are smoking areas, such as designated
             areas in a nonresidential facility, or residential apartments where the occupants may wish