Page 259 - Fluid Power Engineering
P. 259

226   Chapter Eleven


                    various parameters on the line like voltage, current, and fre-
                    quency in order to connect or disconnect the left-hand side
                    components from the transformer.
                  4. Three-phase transformer to raise voltage from low (LV) to
                    medium voltage (MV). Typically, this transformer will in-
                    crease the voltage from 480 or 690 V (depending on gener-
                    ator) to 11 or 69 kV (depending on design of MV line inside
                    the wind farm). The capacity of the transformer is specified in
                    terms of MVA, which is the product of the maximum voltage
                    and maximum current from the generator. In simple terms,
                    the MVA number is 15–25% higher than the rating of the gen-
                    erator. If the turbine is rated 2 MW, then a transformer rating
                    from 2.3 to 2.5 MVA may be chosen. These ratings also apply
                    to almost all components like the circuit breaker, fuses, and
                    metering equipment.

                 Another example of a single-line diagram that covers the entire
              wind farm is in seen in Fig. 11-3. In this diagram, the following com-
              ponents are illustrated:












                     IED       MV to HV   IED

                              Transformer
                                                        Radial feeders
                 Circuit                 Circuit
                 Breaker                Breaker
                         Meter


             Grid






                                                            WTGs

              FIGURE 11-3 Single-line diagram of a wind farm in a radial topology. Individual
              turbines are connected to a radial feeder.
   254   255   256   257   258   259   260   261   262   263   264