Page 263 - Fluid Power Engineering
P. 263

230   Chapter Eleven


              the power factor is 70%, although the generators, transmission, and
              other components are running at full capacity (10 MVA), the system
              is delivering only 7 MW of real power; the rest is reactive power or
              “wattless power” that performs no work. All the components are at
              full capacity or fully loaded in this system because the maximum
              amount of current is flowing through the system causing losses of
              2
             i R t with an appropriate amount of temperature rise. In this situation,
              despite current flow at full capacity, only 70% of real power that is
              expected at the consumption point is, in fact, delivered. Suppose a
              load in this system requires 9.5 MW of real power. In order to satisfy
              this load, 9.5/0.7 = 13.5 MVA of total apparent power is required. This
              will overload the 10 MVA system. The solution to low power factor
              is to install VAR compensators at appropriate points in the system in
              order to deliver higher amount of power to loads.
                 An induction generator demands reactive power of the order of
                 7
              30% of its rated kVA from the grid. See Fig. 11-4 for an illustration of a
              power factor as a function of slip for a squirrel cage induction genera-
              tor. In normal operating conditions, the generator operates at a slip of
              about 5%, where the power factor is about 80 to 90%. At partial loads,
              slip is smaller and the power factor may be 50% or lower. This de-
              mands50%ormorereactivepower.Onemethodtoimprovethepower
                                               8
              factor is to use Static VAR compensator . It is a capacitor in parallel
              with an adjustable inductor. With a 10 MVAR capacitor and 10 MVAR
              inductor, reactive power ranging from 0 to 10 MVAR can be provided.


                −1  −0.8  −0.6  −0.4  −0.2  0   0.2  0.4  0.6   0.8  1
                                                                  Slip
               0.2
                  Generator                                  Motor
               0.4

                              Rated Condition
               0.6

               0.8
                                             Max Power factor=0.88
               Power Factor                Torque
                1






              FIGURE 11-4 Power factor and torque curves for a squirrel-cage induction
              generator. In this illustration, the generator is rated at 5% slip and a power
              factor of 88%. At lower slip and lower torque the power factor is 50% or
              below. 10
   258   259   260   261   262   263   264   265   266   267   268