Page 91 - Wire Bonding in Microelectronics
P. 91

70    Cha pte r  T h ree


              data on varying bare-wire length in the short length region less
              than ~1 mm (where more heat is conducted out through the welds
                                                         2
              on the end). Also, the shorter the wire, the less total I R heating is pro-
              duced in that wire, as stated previously.
                 A graph of experimental data for DC-ramped-current wire-burn
              out for both gold and aluminum wires having wedge bonds (or equiv-
              alent) at each end is given in Fig. 3-9. Two short-wire-length data
              points are included in the figure for comparison. The bond-length ver-
              sus current transition is actually a continuous one. The data that are
              available indicate that for 25-µm diameter bare gold wire, the burnout
              current decreases continuously as the wire is lengthened (from ~1.8 A
              at 1 mm length) and reaches approximate equilibrium for lengths
              more than or equal to 5 mm (at ~0.6 A). The long-wire minimum burn-
              out current is similar to that reported in [3-25, 3-30, 3-33]. See Fig. 3-10
              for a calculated example of the burn-out current versus length for both
              Au and Al wires, showing clearly the decrease in burn-out current
              with increased length. Normally one may assume that wires contain-
              ing the traditional <10 ppm impurities will have the same burn-out
              properties as pure  Au (calculated in Fig. 3-10 (up to 1%) which
              increases the resistivity and can reduce the burn-out current for a
              given situation. Note also that burn-out current can be much greater
              when wires are plastic encapsulated.


                                    Wire bond length (mils)
                      0   40  80       160     240      320      400

                             Calculated burn-out current in air for gold and
                     3       aluminum wires of 25 µm diameter at 20°C
                                                 –4
                   Burn-out current (l b ) (amps)  2  Au
                             (l  of Au decreases ~ 2 × 10  A/°C for
                              b
                             range 20°–150°C)




                     1




                     0            Al
                      0   0.1  0.2  0.3  0.4    0.6     0.8      1.0
                                     Wire bond length (cm)
              FIGURE 3-10  Wire burnout calculated for pure Au and Al, 25 µm wires
              using the resistivity of pure Al and Au. This compares adequately with data
              in Fig. 3-9, considering that both measured material were doped, and the
              diameters may vary by 3–5%, whereas the  curves use pure metal data and
              exactly 25 µm diameters.
   86   87   88   89   90   91   92   93   94   95   96