Page 219 - A Practical Companion to Reservoir Stimulation
P. 219

PRACTICAL COMPANION TO RESERVOIR STIMULATION






















            Figure P-62-Flapper-style  check valve in the closed   Figure P-63-Dart-style  check valve in the closed position.
            position.



            for controlling the well when there is a sudden loss of pump   diverter can be included on the wellhead side of the choke to
            pressure, such as when  a treating line fails. In  these emer-   catch the balls and prevent  them from interfering with  the
            gency  situations  there  is  no  time  to  physically  close  the   bleedoff procedure. The bleed line should tee off of the main
            wellhead valves, but the check valve can automatically close   treating  line  and  be  staked  (Fig.  P-64).  Lateral,  or  “Y,”
            almost instantaneously.                              connections should be avoided when laying the bleed line. A
              Two common  types  of  check  valves are  used  in  high-   bleed line using a lateral is difficult to stake in place and may
            pressure treating lines. Flapper-type check valves (Fig. P-62)   move when  the bleed  valves are opened and there  is high
            are usually used  in the main treating line. Proppants, solid   pressure at the wellhead.
            diverting agents and ball sealers can all be pumped through
            this style of valve without fear of plugging or destroying its   P-7.1.4: Measuring Pressure
            reliability. Dart check valves (Fig. P-63) are used in nitrogen   It  is  imperative  that  the  treating  pressures  be  accurately
            and COz treating lines. These valves use a spring to seat a dart   known during a treatment. The main sensor used to measure
            and  close  the  valve  when  injection stops. The  dart  check   the  pressure  should be  placed  as  near  to  the  wellhead  as
            valve  is easily cut  by  proppants and  plugged by  diverting   practically possible. Care should be taken to locate the pres-
            agents; it  is not  recommended for use in the main treating   sure sensor on the wellhead side of the check valve to ensure
            line.                                                that an accurate pressure is available even after the pumping
                                                                 operations have stopped. Should the transducer inadvertently
            P-7.1.3: Bleedoff Lines                              be placed on the upstream side of the check valve, pressure
            A bleedoff line is used to relieve pressure from the system of   readings could indicate that  pressures have bled off  while
            high-pressure treating lines once the wellhead valves have   actual wellhead pressures remain dangerously high.
            been closed. This line is not intended for extended flowback   Generally, there will be several pressure sensors available
            of well fluids. A permanent flowback line should be laid for   for monitoring purposes in addition to the primary transducer
            long-term flow  of  well  fluids. This  line  should be  placed   at the wellhead. A second transducer should be identified and
            between the check valve and the wellhead control valve. If   calibrated to the primary sensor. Pressure measurements from
            the bleedoff arrangement is misplaced, pressure will be trapped   this  transducer should be  used  if  the  primary  sensor fails
            between the wellhead  and the check valve, and a pressure   during the treatment. All pump trucks should have a trans-
            hazard will result when the treating line is rigged down.   ducer on each high-pressure pump. However, these sensors
              A choke and double-valve arrangement should be “teed”   should not  be  used  as the backup to the  primary  pressure
            off of the main treating line to start the bleed line. One valve   transducer. The pumps may  need to be  shut in and isolated
            serves as a master valve that  is always fully open or fully   during the treatment, which will result in a loss of pressure
            closed and is opened first and closed last. The second valve is   measurements. The pump sensors may be  used  to indicate
            slowly opened and closed to control the flow of fluid. Swivel   problems associated with each unit. A pressure that deviates
            joints should be avoided in a bleed line. When a turn in the   significantly from the  other sensors indicates that  a pump
            line is necessary, teed connections should be used. This line   needs  to  be  shut  in  and  isolated. Once  the  source of  the
            must  be  restrained every  15  ft to  20  ft to prevent  it  from   abnormal pressure is located and repaired, the pump may be
            moving. Care should be taken when flowing back fluids that   brought back on line.
            could potentially be carrying ball sealers. A ball sealer flow


            P-58
   214   215   216   217   218   219   220   221   222   223   224