210 Advanced Design Examples of Seismic Retrofit of Structures
























            FIG. 4.10 An example of the infill wall with sold bricks and sand-cement mortar. (Permission
            from DRES.)


            Field observations of the infill walls indicate that the quality of brick work in the
            example building is fair to good; hence, according to ICERIFB [2], the expected
            compressive strength of the masonry prism (f me ) and the expected shear strength
            of mortar (v me ) are 5.000MPa and 0.165MPa, respectively. The modulus of
            elasticity of the masonry prism is:
                              E me ¼ 550f me ¼ 550 5 ¼ 2750MPa          (4.5)
            4.4.1.4 Conditions for Activation of Infill Wall Behavior
            At this stage, it is assumed that all the frame members can acceptably tolerate
            the forces from the infill walls. The acceptance criteria for each frame member
            are checked in Section “The Results” and, if vulnerable, proper retrofit solution
            is proposed to upgrade these members.
               According to ICERIFB [2], each wall should have all of these conditions in
            order to be considered as an infill wall:
            l The wall shall have adequate strength to when subjected to out-of-plane
               force. By assuming the arching action in the walls, the lower-bound out-
               of-plane strength of the infill panel is determined using Eq. (4.6).


                                        0:7f mL λ 1 λ 2
                                   Q CL ¼         144                   (4.6)
                                           h inf
                                           t inf
            where:
               f mL ¼lower bound of masonry compressive strength;
               λ 1 ¼slenderness parameter as defined in Table 4.1;