Page 307 - Advances in Renewable Energies and Power Technologies
P. 307

280    CHAPTER 8 Hybrid PV/Batteries Bank/Diesel Generator




                                                    Bus DC         Bus AC


                                                                               Load
                                                  DC/DC

                               Photovoltaic Panel
                                                               DC/AC
                                 Batteries      DC/DC
                                                                              Diesel
                                                                             Generator




                                                       Control System
                         FIGURE 8.18
                         Hybrid PV/batteries bank/diesel generator renewable energy system block diagram.

                         4.2.1 Batteries Bank Depth of Discharge Control
                         Lead-acid batteries are used in the hybrid renewable energy system to store electrical
                         power. Typically, batteries maximum dod value is set to 80% to protect batteries from
                         over discharging, which affect the batteries lifetime. On the other hand, the minimum
                         dod value at which the DG is turned OFF needs to be adjusted to achieve the best
                         cost/pollution results [7]. Thus, the dod value must be in the range defined as:

                                                 dod min < dod < dod max               (8.29)
                         The battery dod value is computed using Eq. (8.6).

                         4.2.2 AC Load Prediction
                         The load used in this management scheme represents a typical house in Tunisia as
                         described in Section 3. The required load power can be supplied during the night by
                         the DG through the AC bus or by the batteries storage bank through a DC/AC
                         inverter as shown in Fig. 8.18. An autoregressive moving average (ARMA) scheme
                         associated with a Kalman filter is adopted in this management process to forecast the
                         load every 2 min ahead of the actual load value. During the day, the actual measured
                         load at each 2 min are used as input to the ARMA algorithm. The obtained modeled
                         values and actual load values are used in Kalman filter to predict the load every
                         2 min ahead of operation. Fig. 8.19 describes the steps of the ARMA prediction
                         algorithm.

                         4.2.3 Energy Management Process
                         PSO algorithm is used for sizing the investigated hybrid renewable energy system as
                         described above [9]. The achieved optimal system sizing for minimum overall sys-
                         tem cost and emitted pollution corresponds to 10 batteries with total capacity of
   302   303   304   305   306   307   308   309   310   311   312