288 CHAPTER 8 Hybrid PV/Batteries Bank/Diesel Generator
Table 8.11 Summary of Hybrid System Operation Results for dod Set Range
Value of 0%e80% for Minimum Pollution Analysis Condition
Number of discharging cycles of batteries 5
Diesel engine operation time 7 h 36 min
Number of cycles of DG 2
Diesel consumption (L) 23.688
CO 2 emission (Kg) 17.055
(A)
20
load(Kw) 10
0
(B)
100
dod % 50
0
(C)
20
diesel output power (kW) 10
0
6 11 16 21 2 6 12 18
hours
FIGURE 8.23
Results for dod range of 0%e80% when minimum pollution analysis condition. (A) AC
load power requirements over 36 h. (B) dod status of the batteries. (C) diesel generator
(DG) output power.
Table 8.12 Summary of Hybrid System Operation Results for dod Set Range
Value of 0%e80% for Minimum Cost Analysis Condition
Number of cycles of operating the batteries 6
Diesel engine operation time (h) 9
Number of cycles of DG 4
Diesel consumption (L) 24.32
CO 2 emission (kg) 17.51