Page 153 - Boiler_Operators_Handbook,_Second_Edition
P. 153

138                                                                               Boiler Operator’s Handbook

               special requirements for one of those boilers.       ONCE THROUGH BOILERS
                    A waste heat boiler will always have a lot more
               heat exchange surface than a fired boiler because there     I am aware of one manufacturer of once through
               is no radiant heat transfer. It’s safe to assume a waste  boilers in the commercial to industrial range and many
               heat boiler will have twice the heating surface of a con-  electric utility boilers are designed for once through op-
               ventional boiler for the same capacity. It isn’t uncom-  eration. The boiler feed pump(s) or a boiler water circu-
               mon to encounter a waste heat boiler with finned tubes  lating pump is used to produce the differential pressure
               to provide additional heating surface so you will not  required to force the water and steam through the boiler.
               necessarily encounter boilers with twice the number of  Similar to HTHW generators these boilers can contain
               tubes. Depending on the source of the heat the boiler can  multiple circuits of tubing with inlet and outlet headers
               incorporate an economizer section to preheat the feed-  but many have one single circuit to maintain a point of
               water and can be of once through design. The materials  conversion from saturated to superheated steam. Feed
               of construction may include materials that don’t con-  water is forced into the tubes and steam which may be
               form to the requirements of the Rules for Construction  saturated or superheated leaves the tubes. All electric
               of Heating Boilers (Section IV) or Rules for Construc-  utility boilers of this design generate superheated steam.
               tion of Power Boilers (Section I) because the liquids or  Needless to say, those boilers must use absolutely pure
               gases that are the source of the heat would destroy those  water because any dissolved solids would build up in the
               materials. In those cases the boilers are constructed in  boiler tubes as scale.
               accordance with the Rules for Construction of Pressure     Once through boilers that generate saturated steam
               Vessels (Section VIII) as an “unfired boiler” which al-  also incorporate a steam and water separator at the outlet
               lows use of exotic materials including stainless steels,  so only steam is delivered to the facility. The water that
               Inconel, and others.                                 exits the boiler with the steam is separated and returned
                    The largest, physically, waste heat boiler I ever  back to the inlet of the circulating pump. The one boiler
               encountered was one I helped design and, as far as I  design I know of has only one tube formed into a long
               know, is still in service in Wilmington, North Carolina.  coil that surrounds the boiler furnace and may have addi-
               It is twenty-four feet in diameter, over ninety feet tall  tional tubing extending the coil as a convection section. A
               and generates about 25,000 pph of low pressure steam.  safety feature on these boilers, that doesn’t exist on other
               The largest in capacity is a unit that looks more like an  types, consists of a switch activated by the thermal expan-
               economizer and only preheats boiler plant makeup wa-  sion of one of the boiler tubes. If there is insufficient water
               ter, 120 million Btuh. They come in a variety of sizes and  flow through the tube its coil expands as it is heated to
               configurations that are so variable that there’s no de-  trip the switch.
               scribing them all and their operation varies significantly     Flow has to be proven before lighting a fire in one of
               depending on the conditions of the fluid flow stream the  these boilers so treat the low water flow switch with the
               heat is coming from.                                 same concern and testing as a low water cutoff.
                    A low water cutoff is a required element for any
               boiler and they should always be provided on waste
               heat boilers unless the temperature of the fluid stream  ENGINES AND EMERGENCY GENERATORS
               is less than about 750°F where the metal will not
               overheat. I can recall one system where a contractor     At the risk of being called overly emphatic I will
               installed a waste heat boiler connected directly to the  repeat that you should never operate equipment until
               exhaust of a steel annealing furnace which exhausted  you’ve read the instruction manual. These guidelines
               a heating stream at about 1800°F. The new boiler was  only apply if you can’t find the manual, something that
               melted down two days after installation because the  happens with surprising regularity.
               water source failed. If the temperature is high enough     The most common engine in a boiler plant is nor-
               there should always be a way of diverting the waste  mally the emergency generator. For reasons that still
               heat stream to prevent overheating the boiler. In some  escape me ships, from other nations, which I visited
               cases there is no diversion of the waste heat stream but  during my tenure in the merchant marine were almost
               it’s possible to add air to dilute it until the boiler metal  always powered only by engines. I enjoyed taking tours
               can withstand the temperature. With those exceptions  of those ship’s engine rooms to see diesel engines so
               any waste heat boiler should be treated like a normal  large that you could stand inside one of the cylinders
               boiler.                                              and fuel injectors that were so large it took two men to