Page 271 - Boiler plant and distribution system optimization manual
P. 271

256                                                 Boiler Plant and Distribution System Optimization Manual


                     Severe damage can occur when the incom-        generator operating procedures may also have to
                pressible slug of water is forced to change direc-  be investigated and changed.
                tion by a pipe bend, fitting or valve. It produces       All of the steam generated by the boiler must
                a  shock  wave  of  tremendous  momentary  force    eventually leave the system as condensate, except
                which  can  cause  great  physical  damage.  It  is  a   for leaks and steam directly used for some pur-
                function  of  the  mass  of  water  and  the  velocity   pose. It is obvious that if the steam can somehow
                squared, so the greater part of its energy comes    escape from the system without going through a
                from the high velocities (6,000-12,000 feet per     trap as condensate, the system will be inefficient
                minute) achieved in the steam piping.               to that degree. Properly working traps insure that
                     Some steam boilers have a tendency to pro-     steam gives up its energy efficiently.
                duce  low  quality  steam,  which  contains  an  ap-
                preciable amount of moisture and possibly boiler    Air and Noncondensibles in the
                chemicals and contaminated boiler water. This in-   Steam System
                troduces water into the boiler header and distri-        Accumulations of air and  noncondensible
                bution piping. Depending on the severity, this can   gases in the steam system can limit steam flow,
                overload the distribution and trapping systems.     steam temperature and heat energy release. Air
                     To detect this problem a Throttling Calorim-   is present in the system on startup and is intro-
                eter can be used to test for steam quality (percent   duced through vacuum breakers.
                moisture in the steam). This instrument measures         Noncondensible gases are liberated in the
                the temperature of a very small amount of steam     boiler. Carbon dioxide and oxygen are dissolved
                discharging from the steam main. Dry steam will     in  boiler feedwater  as  carbonates and bicarbon-
                become superheated due to the pressure drop. If
                there is any moisture present, the temperature of
                the  discharge  will  be  reduced.  Measuring  tem-
                perature and comparing it to the maximum pos-
                sible temperature will indicate steam quality.
                     Other methods that can be used are:


                a.   Ion exchange


                b.   Conductivity

                c.   Sodium tracer flame photometry

                d.   Specific ion electrodes.


                     These methods determine the solids content
                of the steam, including the solids carried over by
                water droplets.
                     The throttling steam calorimeter is the only
                direct way to determine steam quality and is most
                accurate below 600 psi and where moisture con-
                tent is above 0.5 percent.
                     When low water quality is detected, it indi-
                cates a problem with the water level control, feed-
                water treatment, blowdown cycle, boiler sizing or   Figure 14.4—Shows several forms of steam and con-
                steam drum internal problems. Boiler and steam      densate mixing in piping.
   266   267   268   269   270   271   272   273   274   275   276