Page 137 - Chemical engineering design
P. 137

FUNDAMENTALS OF ENERGY BALANCES
                   of a negative value in the column indicates that the temperature gradient is in the wrong
                   direction and that the exchange is not thermodynamically possible.     117
                     This difficulty can be overcome if heat is introduced into the top of the cascade:
                     6. Introduce just enough heat to the top of the cascade to eliminate all the negative
                   values; see Figure 3.23b.
                     Comparing the composite curve, Figure 3.22, with Figure 3.23b shows that the heat
                   introduced to the cascade is the minimum hot utility requirement and the heat removed at
                   the bottom is the minimum cold utility required. The pinch occurs in Figure 3.23b where
                   the heat flow in the cascade is zero. This is as would be expected from the rule that for
                   minimum utility requirements no heat flows across the pinch. In Figure 3.23b the pinch
                                          Ž
                   temperatures are 80 and 90 C, as was found using the composite stream curves.
                     It is not necessary to draw up a separate cascade diagram. This was done in Figure 3.23
                   to illustrate the principle. The cascaded values can be added to the problem table as two
                   additional columns; see example 3.16.


                   Summary
                   For maximum heat recovery and minimum use of utilities:
                     1. Do not transfer heat across the pinch
                     2. Do not use hot utilities below the pinch
                     3. Do not use cold utilities above the pinch



                   3.17.3. The heat exchanger network
                   Grid representation
                   It is convenient to represent a heat exchanger network as a grid; see Figure 3.24. The
                   process streams are drawn as horizontal lines, with the stream numbers shown in square
                   boxes. Hot streams are drawn at the top of the grid, and flow from left to right. The cold
                   streams are drawn at the bottom, and flow from right to left. The stream heat capacities
                   CP are shown in a column at the end of the stream lines.



                                                                  Cooler
                                                     A
                                   Hot stream  n
                                   no. n
                                                     A               Cold stream
                                                                  m   no. m
                                                   Exchanger

                                             Figure 3.24.  Grid representation


                     Heat exchangers are drawn as two circles connected by a vertical line. The circles
                   connect the two streams between which heat is being exchanged; that is, the streams that
                   would flow through the actual exchanger. Heater and coolers are drawn as a single circle,
                   connected to the appropriate utility.
   132   133   134   135   136   137   138   139   140   141   142