Page 177 - Decision Making Applications in Modern Power Systems
P. 177

TABLE 5.2 Max 611-bus voltage with various Volt/Var
                   controlling the system.
                   Bus with Volt/Var control  Maximum voltage 611-bus (p.u.)
                   611                       1.0648
                   611 680                   1.0618
                   611 675                   1.0549
                   611 671                   1.0562
                   611 680 675               1.0544
                   611 680 671               1.0554
                   611 671 675               1.0529
                   611 680 675 680           1.0528
                   611 646                   1.0546
                   611 634                   1.0641
                   611 646 634               1.0544
                   611 646 675               1.0489
                   611 646 671               1.0495
                   611 646 680               1.0528
                   All buses                 1.0526
                   Note: Bold represents the identify the lowest voltage levels.


                                       Voltage V3 bus 611
                  1.08
                                                                   VVred
                                                                   VSto
                  1.06
                            Upper limit
                  1.04

                 Voltage (p.u.)  1.02 1






                  0.98


                  0.96
                            Lower limit
                  0.94
                     0          5         10         15         20
                                             Hours
             FIGURE 5.16 611-Bus voltage with storage insertion.
   172   173   174   175   176   177   178   179   180   181   182