Page 298 - Decision Making Applications in Modern Power Systems
P. 298

258  Decision Making Applications in Modern Power Systems


            in an actual power system scenario, upper and lower limits (9 36 MVar) are
            adopted for the redispatch of each generator.
               It is possible to verify that the dispatch of reactive power for all intervals
            reached the objective function of loss reduction for the system. Analyzing
            the scenarios separately, A1 obtained greater loss reduction, whereas A17
            presented the greater increase of load margin. Then, comparing the gains for
            each system, A17 is the scenario that presented the greater dispatch benefit.
               The PV curves for the critical buses depicted in Table 10.1 concerning all
            intervals before and after optimization are illustrated in Figs. 10.4 10.14.


                        41     39   117    33    2     35    3    13
                       0.98

                       0.96
                       0.94
                      V (p.u.)  0.92


                        0.9

                       0.88

                          0      0.2     0.4     0.6     0.8
                                           Lambda
            FIGURE 10.4 PV curves—base case.



                     41    39    35    43    33    37    88    53
                    0.98

                    0.96

                   V (p.u.)  0.94
                    0.92
                     0.9

                    0.88
                    0.86
                       0      0.2     0.4    0.6     0.8     1
                                         Lambda
            FIGURE 10.5 PV curves—A1, prior-dispatch.
   293   294   295   296   297   298   299   300   301   302   303