Page 184 - Defrosting for Air Source Heat Pump
P. 184

178                                         Defrosting for Air Source Heat Pump


          Table 6.5 Results of the three experimental cases
          Item   Parameter       Case 1           Case 2          Case 3

          1      Melted frost    374 g            330 g           317 g
                 collected from
                 Circuit 1
          2      Melted frost    329 g            362 g           328 g
                 collected from
                 Circuit 2
          3      Melted frost    297 g            360 g           324 g
                 collected from
                 Circuit 3
          4      FEC             79.4%            91.2%           96.6%
          5      Total mass of   1000 g           1052 g          969 g
                 melted frost
                 collected
          6      Results shown in  Figs. 6.27, 6.30,  Figs. 6.28, 6.31,  Figs. 6.29,
                                 6.33, 6.34,      6.33, 6.35,     6.32, 6.33,
                                 6.37–6.40        6.37–6.40       6.36–6.40



         the FEC, as many parameters affect frosting performance. However, in this section,
         modulating valves installed at an inlet refrigerant pipe to each circuit may be deployed
         to vary the refrigerant flow to each circuit, and thus the frost accumulation on each
         circuit is adjusted. Therefore, to adjust the refrigerant flow into each circuit, a series
         of trial-and-error manual adjustments of the opening degrees of the stop valves was
         carried out. Then, a set of fixed valve opening degrees was obtained, and frost
         accumulated on the surface of an outdoor coil at different FECs could be reached.
         Thereafter, the FEC was calculated by the mass of melted frost collected from
         water-collecting cylinders, with the water vaporized into the ambient air neglected.
         During the experiments, water-collecting trays were installed to collect the melted
         frost from its upside circuit. Finally, experimental work was carried out on three
         experimental cases, as listed in Table 6.5, so the system defrosting performances at
         different FECs with melted frost local drainage could be comparatively and quantita-
         tively analyzed.



         6.4.2 Experimental results
         Fig. 6.26 presents three photographs showing the airside surface conditions of the out-
         door coil at the start of defrosting operations in the three cases. As observed from these
         pictures, the surface conditions at the start of defrosting for each circuit in the three
         cases were visually the same, which agreed well with the frost accumulated on the
         surface of each circuit, as listed in Table 6.5. Moreover, it could be found that it is
         hardly possible to visually distinguish the difference of FECs among the three cases,
         although their values are calculated totally differently. Therefore, the study on
   179   180   181   182   183   184   185   186   187   188   189