Page 194 - Defrosting for Air Source Heat Pump
P. 194

188                                         Defrosting for Air Source Heat Pump

         surrounding air temperature. This also demonstrated that the melted frost temperature
         is mainly affected by the later melted frost flowing into the cylinder.
            Fig. 6.38 presents the measured refrigerant volumetric flow rate during defrosting
         in the three cases. It is observed that the measured refrigerant volumetric flow rate
         keeps fluctuating severely from 0 to 80 s, especially during the first 40 s into
         defrosting. This is because the compressor discharge pressure increased suddenly
         at the start of an RCD operation, and the internal diameter of the EEV is very small.
         In addition, a lot of energy is consumed during defrosting at the frost-melting stage
         described in Chapter 4, with a lot of refrigerant changing phases from the gas state
         to the two-phase state. Therefore, the measured refrigerant volumetric flow rate fluc-
         tuates with severe pressure changes. When the defrosting process came into the water
         layer vaporizing stage described in Chapter 4, the pressures of the compressor suction
         and discharge both increase, leading to the refrigerant volumetric flow rate changing
         from increasing to decreasing. As shown in Fig. 6.38, from 80 to 165 s into defrosting,
         the order of the measured refrigerant volumetric flow rate during defrosting in the
         three cases is R Case 3 > R Case 2 > R Case 1 . This results because the defrosting perfor-
         mance in Case 3 is better than in Case 1, which makes the refrigerant flow rate increase
         earlier. Finally, from Case 1 to Case 3, their peak values came out at 175, 170, and
         165 s, respectively. Here, it is further confirmed that the defrosting performance
         would be improved with a higher FEC as a defrosting start for an ASHP unit with
         a vertically installed multicircuit outdoor coil.



         6.4.3 Durations, energy analysis, and discussions
         Table 6.6 lists the durations for tubes and fins and their DECs in the three cases.
         It could be found that the DEC for tube surface temperature is 97.97% for Case 1,
         97.86% for Case 2, and 98.26% for Case 3, respectively. The DEC for fin surface tem-
         perature is 97.58% for Case 1, 97.01% for Case 2, and 97.83% for Case 3, respec-
         tively. Obviously, the DEC orders of tube and fin surface temperature in the three
         cases are the same, at DEC 3 > DEC 2 > DEC 1 . But the order is different from that

          Table 6.6 Durations for tubes and fins, and the DECs in the three cases
          Item     Parameter                     Case 1     Case 2     Case 3

          1        Duration for tube of Circuit 1  193 s    187 s      174 s
          2        Duration for tube of Circuit 2  197 s    183 s      172 s
          3        Duration for tube of Circuit 3  193 s    186 s      175 s
          4        DEC for tube surface temperature  97.97%  97.86%    98.26%
          5        Defrosting duration (for tube)  198 s    188 s      175 s
          6        Duration for fin of Circuit 1  203 s     195 s      182 s
          7        Duration for fin of Circuit 2  207 s     198 s      184 s
          8        Duration for fin of Circuit 3  202 s     201 s      180 s
          9        DEC for fin surface temperature  97.58%  97.01%     97.83%
          10       Defrosting duration for fin   207 s      200 s      185 s
          11       Duration difference           9 s        12 s       10 s
   189   190   191   192   193   194   195   196   197   198   199