Page 198 - Defrosting for Air Source Heat Pump
P. 198

192                                         Defrosting for Air Source Heat Pump

         should be further studied. At the same time, the relationship between the FEC and
         defrosting performance evaluating indexes could be further analyzed. Second,
         when the FEC was calculated, the order of frost mass accumulation on the three cir-
         cuits was not fixed. For example, the frost accumulation order in Section 6.3 was at
         Circuit 2 > Circuit 1 > Circuit 3 in Case 1, but at Circuit 2 > Circuit 3 > Circuit 1 in
         Case 2. Due to the negative effects of the downward flow of melted frost, the
         defrosting performance would be different for the two cases with the same FEC
         but different frost accumulation mass orders. Therefore, further studies should be car-
         ried out considering the frost accumulation mass order. Third, for an ASHP unit, its
         frosting duration is much longer than its defrosting duration. The FEC effects on a
         frosting-defrosting cycle should be further analyzed before the installation of valves
         in each circuit of the outdoor coil was considered in application. Fourth, uneven refrig-
         erant distribution may also result in uneven defrosting. Further experimental investi-
         gation on the effects of uneven refrigerant distribution during defrosting in an ASHP
         unit with a multicircuit outdoor coil should be carried out.



         References

         [1] Wang W, Feng YC, Zhu JH, Guo QC, Lu WP. Performances of air source heat pump system
            for a kind of mal-defrost phenomenon appearing in moderate climate conditions. Appl
            Energy 2013;112:1138–45.
         [2] Steiner A, Rieberer R. Parametric analysis of the defrosting process of a reversible heat
            pump system for electric vehicles. Appl Therm Eng 2013;61:393–400.
         [3] Yao Y, Jiang YQ, Deng SM, Ma ZL. A study on the performance on the airside heat
            exchanger under frosting in air-source heat pump water heater/chiller unit. Int J Heat Mass
            Transf 2004;47(17–18):3745–56.
         [4] Seker D, Kartas H, Egrican N. Frost formation on fin-and-tube heat exchanges, Part I:
            modeling of frost formation on fin-and-tube heat exchangers. Int J Refrig 2004;27(4):
            367–74.
   193   194   195   196   197   198   199   200   201   202   203