196                                         Defrosting for Air Source Heat Pump


                     40
                               Circuit 1     Circuit 2     Circuit 3
                     36
                   Tube surface temperature ( o C)  28  T    T    T 3
                     32


                     24
                     20
                                               2
                                            1
                     16
                     12
                                       T  > T  > T
                      8                 1  3  2
                               15 s                     110 s
                      4
                       0      20     40      60     80     100    120
                                           Time (s)

         Fig. 7.1 Measured tube surface temperatures at the exits of the three refrigerant circuits on
         defrosting mode without any frost accumulated in Case 1.


                     44
                                Circuit 1     Circuti 2     Circuit 3
                     40

                     36
                    Tube surface temperature ( o C)  28  T  > T  > T 1  T  = T  = T 3
                     32

                                                  2
                                               1
                             2
                                3
                     24
                     20
                     16
                                   10 s       40 s      115 s
                     12
                      8
                       0      20     40      60     80     100    120
                                           Time (s)
         Fig. 7.2 Measured tube surface temperatures at the exits of the three refrigerant circuits on
         defrosting mode without any frost accumulated in Case 2.


         shown that the temperatures were observed at T Circuit1 > T Circuit3 > T Circuit2 from 15 to
         110 s defrosting operation point. However, in Case 2, as shown in Fig. 7.2, the tem-
         peratures of the three circuits were nearly the same from 40 to 110 s. Only during the
         first 40 s were the three temperature curves not coincident while the system was