Page 205 - Defrosting for Air Source Heat Pump
P. 205

The influence of refrigerant distribution on defrosting           199


                       28
                                  Fin in Circuit 1
                       24         Fin in Circuit 2
                                  Fin in Circuit 3
                       20           T  > T ; T  > T 2
                      Fin surface temperature ( o C)  12 8  T  > T  > T 2
                                     3
                                         1
                                          3
                       16
                                                      1
                                                         3



                        4
                                                      210 s     217 s
                        0
                         80   100   120  140  160   180  200  220   240
                                             Time (s)
           Fig. 7.6 Measured fin surface temperature at the center of the three refrigerant circuits during
           defrosting in Case 1.




                       28
                                  Fin in Circuit 1
                       24         Fin in Circuit 2
                                  Fin in Circuit 3
                       20
                      Fin surface temperature ( o C)  12 8  T  > T ; T  > T  2
                       16
                                     3
                                3
                                   1



                        4
                                          165 s            182 s
                        0
                         80   100   120  140  160  180   200  220  240
                                             Time (s)
           Fig. 7.7 Measured fin surface temperature at the center of the three refrigerant circuits during
           defrosting in Case 2.
   200   201   202   203   204   205   206   207   208   209   210