Page 200 - Defrosting for Air Source Heat Pump
P. 200

194                                         Defrosting for Air Source Heat Pump

         vertically installed multicircuit outdoor coil in an ASHP unit during defrosting was
         reported in the open literature.
            For a multicircuit outdoor coil in an ASHP unit, the effects of uneven refrigerant
         distribution on defrosting performance is a fundamental problem. Therefore, in this
         chapter, experimental studies on system defrosting performance when refrigerant
         was evenly or unevenly distributed into each circuit have been carried out. Also, both
         with and without the melted frost being locally drained were considered, and a com-
         parative and quantitative analysis was conducted using the experimental data.


         7.2   Defrosting performance influenced by uneven
               refrigerant distribution

         An experimental study on system defrosting performance when the refrigerant was
         evenly or unevenly distributed into each circuit was first carried out in a novel ASHP
         unit, with the melted frost locally drained by trays. The experimental setup, procedure,
         and conditions were introduced in previous chapters. In this section, the description of
         experimental cases is first reported. This is followed by presenting the experimental
         results, and finally the result analysis and conclusions are given.



         7.2.1 Experimental cases
         A series of experimental works using the experimental ASHP unit has been carried out
         to study the effects of uneven refrigerant distribution due to gravity and tube internal
         resistance on defrosting performance. In order to obtain meaningful experimental
         results, it was necessary to ensure that the frost accumulated on the surface of the three
         circuits was even at first. For an ASHP unit with a multicircuit outdoor coil, it is hard
         to adjust the FEC, as many parameters affect frosting performance. However, in this
         section, modulating valves installed at an inlet refrigerant pipe to each circuit may be
         deployed to vary the refrigerant flow to each circuit, and thus the frost accumulations
         on each circuit are adjusted. Therefore, to adjust the refrigerant flow into each circuit,
         a series of trial-and-error manual adjustments of the opening degrees of the stop valves
         was carried out. Then, a set of fixed valve opening degrees was obtained, and the
         amount of frost accumulation on the three circuits was close to each other, with their
         differences smaller than 10%. As previously mentioned, the FEC was defined as the
         ratio of the minimum frost accumulation among the three circuits to the maximum
         one. The FEC could be calculated by the masses of melted frost collected from
         water-collecting cylinders, with the water vaporized into the ambient air neglected.
            Second, to comparatively study the effects of uneven refrigerant distribution, it was
         necessary to ensure that the evenness of the refrigerant distributed into the three cir-
         cuits during defrosting was different. Due to gravity and tube internal resistance
         directly affecting the refrigerant distribution, it seems hardly possible to adjust the
         refrigerant for even distribution into the three circuits. However, in this section, mod-
         ulating valves installed at an inlet refrigerant pipe to each circuit may be deployed to
   195   196   197   198   199   200   201   202   203   204   205