Page 224 - Defrosting for Air Source Heat Pump
P. 224

218                                         Defrosting for Air Source Heat Pump


          Table 7.7 Different durations, defrosting efficiencies, and relative differences in two
          experimental cases
          Item   Parameter                       Case 1    Case 2   Difference

          1      Duration of tube surface temperature  185 s  173 s  6.5%
                 of Circuit 3 reaching 24°C
          2      Duration of fin surface temperature of  211 s  200 s  5.2%
                 3 circuits all reaching 24°C
          3      Duration of TDOEE reaching its peak  110 s  105 s  4.5%
                 value
          4      Peak value of TDOEE             42.8°C    38.0°C   (4.8)
          5      Duration of TDIEE reaching its peak  25 s  30 s     20%
                 value
          6      Peak value of TDIEE             43.2°C    40.9°C   (2.3)
          7      Duration of refrigerant volumetric flow  160 s  160 s  0
                 rate reaching its peak value
          8      Duration of melted frost reaching the  120 s  115 s  4.2%
                 water collecting cylinder
          9      Temperature of the lowest temperature  0.45°C  0.2°C  (0.25)
                 of melted frost collected
          10     Total energy supply for defrosting  790.5 kJ  691.6 kJ  12.5%
          11     Total energy consumption during  319.9 kJ  331.5 kJ   3.6%
                 defrosting
          12     Defrosting efficiency           40.5%     47.9%     18.3%



         Therefore, it could be speculated that the defrosting durations of the tube and fin could
         be used to compare the defrosting performances for systems with different defrosting
         efficiencies. In addition, for Items 4, 6, and 9, temperature differences were small, espe-
         cially the value of melted frost at just 0.25°C. However, the peak value of the TDOEE
         difference, 4.8°C, as well as their durations’ difference, 4.5%, could also be considered
         comprehensively as one of the system defrosting performance evaluation parameters.
            In conclusion, for an ASHP unit with a vertically installed three-circuit outdoor
         coil, a comparative experimental study on system RCD performance when the refrig-
         erant is evenly distributed into each circuit or not was undertaken, as well as the
         melted frost downward flowing during defrosting. After the study results were ana-
         lyzed, the following conclusions could be drawn: (1) For an ASHP unit with a mul-
         ticircuit outdoor coil, the refrigerant distributed into each circuit would be affected
         by the tube internal resistance and gravity during RCD. And the negative coupled
         effects of MFDF and URD on the system defrosting performance were qualitatively
         confirmed. (2) After the distribution of refrigerant was evenly adjusted, the duration
         of the tube surface temperature of Circuit 3 reaching 24°C decreased from 185 to
         173 s, or a ratio of 6.5%. Meanwhile, the duration of the fin surface temperature of
         three circuits all reaching 24°C decreased from 211 to 200 s, or a ratio of 5.2%.
         (3) As compared with the refrigerant being unevenly distributed into each circuit,
         for an ASHP unit with a vertically installed multicircuit outdoor coil, the total energy
   219   220   221   222   223   224   225   226   227   228   229