Page 222 - Defrosting for Air Source Heat Pump
P. 222

216                                         Defrosting for Air Source Heat Pump


                     7
                              Case 1
                     6
                              Case 2
                     5
                    Temperature ( o C)  4 3  T  > T  2  T  > T 1



                        1
                                          2
                             T    T               T  > T
                     2        1  2                 2  1

                                       90 s
                     1            60 s
                             26 s
                       0     40    80    120   160   200    240   280
                                          Time (s)
         Fig. 7.22 Measured mean temperature of the air surrounding each circuit during defrosting.

         could also directly demonstrate the negative coupled effects of MFDF and URD on
         system defrosting performance. It is obvious that the temperature of the melted frost
         was very low, at around 0.4°C. Before 148 s into defrosting, the temperature of the
         melted frost in Case 2 was lower than that in Case 1. This reflects that the melted frost
         took less heat from the coil in Case 2. After 148 s, the temperature order was changed
         to T 2 > T 1 . This shows that the defrosting operation terminated earlier in Case 2, and
         thus the melted frost was heated by the surrounding air a lot.
            This phenomenon of defrosting operation terminating earlier in Case 2 is also
         shown in Fig. 7.22; from 26 s to the end of defrosting, the temperature of the air sur-
         rounding each circuit in Case 2 was always higher than that in Case 1. Before 90 s into
         defrosting, the difference between the two cases was very small, especially at 60 s into
         the defrosting operation. The temperatures were the same for the two cases because at
         the period of 0–90 s, the melted frost was melting without downward flowing into the
         down-circuits, and a few areas of the fin and coil contacted the surrounding air. This
         figure also shows that the defrosting performance could be improved by evenly
         adjusting the refrigerant distribution when frost evenly forms on the surface of each
         circuit for an ASHP unit.




         7.3.3 Energy analysis and discussions
         During an RCD operation, the energy mainly comes from four sources: the thermal
         energy from the indoor air, the power input to the compressor, the power input to
         the indoor air fan, and the heat stored in the metal of the indoor coil. The last one
         is small, and thus always neglected. All the energy supplied is used to melt frost, heat
         the outdoor coil metal, heat the melted frost and the residual water, evaporate the
   217   218   219   220   221   222   223   224   225   226   227