Page 223 - Defrosting for Air Source Heat Pump
P. 223

The influence of refrigerant distribution on defrosting           217

           retained water on the surface of the outdoor coil, and heat the cold ambient air. Also,
           only the energy consumed in frost melting and water vaporing are big enough and
           calculated, with the sensible heat of the melted frost and surrounding air taken away
           from the outdoor coil neglected. As listed in Table 7.6, the energy supply and con-
           sumption during defrosting in the two cases were summarized, with their defrosting
           efficiencies calculated. As calculated, the total energy used for defrosting was
           790.5 kJ in Case 1, but 691.6 kJ in Case 2, or 12.5% less. It could be found that in
           this experimental study, the main difference came from the thermal energy from
           the indoor air, with a value of 95 kJ difference between the two cases.
              Defrosting efficiency is always used to evaluate the performance of a defrosting
           operation for an ASHP unit. It is defined as the ratio of the actual amount of energy
           consumption required to both melt the accumulated frost and vaporize the retained
           melted frost to the total amount of energy available from an outdoor coil during an
           entire defrosting operation. In this section, the defrosting efficiencies calculated for
           the two cases were 40.5% for Case 1 and 47.9% for Case 2, as listed in Table 7.6.
           Therefore, the negative coupled effects of MFDF and URD on defrosting performance
           for a vertically installed multicircuit outdoor coil were further quantitatively
           demonstrated.
              Furthermore, the different durations, defrosting efficiencies, and relative differ-
           ences in the two experimental cases were also calculated and summarized in
           Table 7.7. The temperature difference values of Items 4, 6, and 9 were directly pres-
           ented. But the difference values of Items 1–3, 5, 7, 8, and 10–12 were shown with their
           ratios. The same as the previous section, they were also defined as the ratios of the
           difference of Cases 1 and 2 to the value of Case 1, and the results are percentages.
           Obviously, the difference of total energy supply in the two cases, 12.5%, was much
           bigger than the differences of the tube and fin defrosting durations, 6.5% and 5.2%.
           Also, the duration difference of TDOEE reached its peak value at 4.5%, and the dura-
           tion difference of the melted frost collected was 4.2%. However, because the
           defrosting performance was better in Case 2, the defrosting efficiency and the duration
           difference of TDIEE reaching peak values and total energy consumption during
           defrosting were negative values, at  18.3%,  20% and  3.6%, respectively.

            Table 7.6 Energy supply, energy consumption, and defrosting efficiency calculation

            Item   Parameter                             Case 1   Case 2   Unit
            1      The energy from indoor air            674.8    579.8    kJ
            2      The power input to compressor         108.9    106.1    kJ
            3      The power input to indoor air fan     6.8      5.7      kJ
            4      The power input to outdoor air fan    0        0        kJ
            5      Total energy supply for defrosting    790.5    691.6    kJ
            6      Energy consumption on melting frost   292.3    291.2    kJ
            7      Energy consumption on vaporizing retained  27.6  40.3   kJ
                   water
            8      Total energy consumption during defrosting  319.9  331.5  kJ
            9      Defrosting efficiency                 40.5%    47.9%    –
   218   219   220   221   222   223   224   225   226   227   228