Page 282 - Defrosting for Air Source Heat Pump
P. 282

276                                         Defrosting for Air Source Heat Pump












            1A           2A           3A            4A           5A








            1B           2B           3B            4B           5B









            1C           2C           3C            4C          5C









            1D           2D           3D            4D           5D
         Fig. 9.18 Outdoor coil airside surface conditions during defrosting in the five cases. (1A)
         FEC ¼ 93.6% in Case 1, (2A) FEC ¼ 95.6% in Case 2, (3A) FEC ¼ 96.6% in Case 3, (4A) FEC
         ¼ 93.8% in Case 4, (5A) FEC ¼ 97.5% in Case 5; (1B) 15 s in Case 1, (2B) 15 s in Case 2, (3B)
         15 s in Case 3, (4B) 15 s in Case 4, (5B) 15 s in Case 5; (1C) 35 s in Case 1, (2C) 40 s in Case 2,
         (3C) 45 s in Case 3, (4C) 64 s in Case 4, (5C) 96 s in Case 5; (1D) 86 s in Case 1, (2D) 93 s in
         Case 2, (3D) 95 s in Case 3, (4D) 112 s in Case 4, (5D) 114 s in Case 5.


         collected were 805 g in Case 1, 933 g in Case 2, 969 g in Case 3, 1001 g in Case 4, and
         1074 g in Case 5, respectively. These experimental results are summarized in
         Tables 9.3 and 9.4. It could be demonstrated that the frost accumulation is not propor-
         tional to the frosting duration. This also reflects the inaccuracy of a time-based initi-
         ation defrosting control strategy. Therefore, experimentally investigating the frost
         accumulation influence on RCD performance for an ASHP unit is meaningful.
            Fig. 9.19 shows the measured tube surface temperature at the exit of each circuit
         and their average values during defrosting in the five cases. It could be found that from
   277   278   279   280   281   282   283   284   285   286   287