Page 283 - Defrosting for Air Source Heat Pump
P. 283

Defrosting control strategy                                       277


            Table 9.4 Experimental results in the five cases
            Item  Durations        Case 1 (s)  Case 2 (s)  Case 3 (s)  Case 4 (s)  Case 5 (s)
            1     Time of preheating  35    40       45       64        96
                  stage terminated
            2     Time of the melted  86    93       95       112       114
                  frost flowing away
                  from tray
            3     Defrosting duration  153  160      172      180       189
            4     Duration calculated by  150  159   170      179       188
                  average value
            5     Duration calculated by  149  155   171      174       186
                  outdoor coil
                  temperature



           Fig. 9.19A–E, the temperature curves of the lowest circuit, Circuit 3, in the five cases
           started increasing at 85, 100, 100, 105, and 110 s into defrosting. Obviously, the delay
           results from their different frost accumulations. This figure also shows the defrosting
           terminations in the five cases, at 153 s in Case 1, 160 s in Case 2, 172 s in Case 3, 177 s
           in Case 4, and 189 s in Case 5, respectively. The less the frost accumulation is, the
           shorter the defrosting duration. Meanwhile, as shown in Fig. 9.19F, the duration
                                                                             °
           for the average temperature values of each circuit in the five cases reaching 24 C
           shows the same status. It is 150 s in Case 1, 159 s in Case 2, 170 s in Case 3, 179 s
           in Case 4, and 188 s in Case 5, respectively. The durations for their average temper-
           atures are about 1–3 s earlier than those temperatures at the exit of Circuit 3. This is
           reasonable because the temperatures of the up-circuits always increase a little quicker
           than the lowest circuit due to the downward flowing of the melted frost. In addition,
                                            °
           part of temperature curve is lower than 0 Cin Fig. 9.19, especially in Fig. 9.19E. It
                                                                °
           results from the refrigerant temperature being much lower than 0 C during frosting.
           The exit of the outdoor coil during defrosting is just the entrance during frosting. That
           means the defrosting preheating stage was also prolonged by more frost accumulation.
           This also meets Fig. 9.18.
                                                      °
              As shown in Fig. 9.20, the durations of reaching 24 C for the measured tube surface
           temperature at the entrance of the outdoor coil during defrosting in the five cases are at
           149, 155, 171, 174, and 186 s, respectively. Clearly, the differences of the five curves
           are unequal. The curve of Case 4 was much earlier than that of Case 3. This is because
           of the lower FEC in Case 4, at 93.8%. It was much lower than the FECs in Cases 3 and
           5. In fact, when the FEC is lower, the temperature curve should be delayed and exper-
           imentally investigated. However, it is the opposite phenomenon shown in Fig. 9.20.
           Authors demonstrated that it results from the uneven distribution of the refrigerant
           during defrosting in this three-circuit outdoor coil. The same as the previous results,
           as frost accumulation increases from Case 1 to Case 5, the start curve becomes lower,
                        °
           and lower than 0 C for Cases 4 and 5 before 100 s into defrosting. Clearly, Case 2 has
           the best performance in the temperature increase process during defrosting. Addition-
           ally, in Table 9.4, the defrosting duration is calculated with the tube surface of the
   278   279   280   281   282   283   284   285   286   287   288