Page 333 - Defrosting for Air Source Heat Pump
P. 333

328                                         Defrosting for Air Source Heat Pump


          Table 10.9 Experimental results of the four defrosting cases.
          Item   Parameters              Case      Case      Case     Case
                                         D1        D2        D3       D4

          1      FEC of outdoor coil     82.6%     79.4%     96.6%    96.6%
          2      Total frost accumulation  878 g   1000 g    881 g    969 g
          3      Defrosting duration     205 s     197 s     185 s    175 s
          4      Total power inputs      124.6 kJ  128.0 kJ  107.6 kJ  117.3 kJ
          5      Energy from indoor air  666.1 kJ  673.7 kJ  541.2 kJ  561.5 kJ
          6      Condition shown in      (A)       (B)       (C)      (D)
                 Fig. 10.16
          7      Results shown in Fig. 10.18  (T1)  (T2)     (T3)     (T4)



         (1) Fundamental assumptions
         In this work, the following nine fundamental assumptions were first given:

           i. Installation, running, and maintenance costs of solenoid valves and the water-collecting
             trays in the three-circuit outdoor coil were neglected.
           ii. Service life of an ASHP unit was assumed to be 15 years, and the unit price of electricity at
             0.9 CNY/kWh [16].
          iii. In the whole service life of an ASHP unit, three operating seasons were divided: the
             heating season with frost formation, the heating season without frost formation, and
             the cooling season.
           iv. Durations of three operating seasons were constant, and assumed as the climate conditions
             of Beijing (Heating season: Nov. 15–Mar. 15).
           v. In the heating season with frost formation, the duration of a frosting/defrosting cycle was
             assumed at 70 min.
           vi. In a frosting/defrosting cycle, the frosting duration was fixed at 60 min, and two periods of
             3–4 min for compressor shutdown were left for its safety, as illustrated in Fig. 10.17 (To
             avoid an undesired shutdown for the ASHP unit, the frosting duration was not longer than
             60 min in practical application).
          vii. Defrosting durations in the four typical cases, system COP, and defrosting efficiency were
             constant.
          viii. All ambient air parameters, such as air temperature and relative humidity, were constant at
             fixed operating seasons.
           ix. For the cases without valves installed, their FECs were fixed at 75.7%. For the cases with
             valves installed, their FECs were fixed at 96.6%.


         (2) Frosting assumptions

         To calculate the running cost at the frosting stage, the system COP and indoor heat
         supplied should be obtained. Therefore, the following assumptions were also given.
           i. Durations of the heating season with frost formation and the heating season without frost
             formation were both assumed to be 60 days/year.
   328   329   330   331   332   333   334   335   336   337   338