Page 334 - Defrosting for Air Source Heat Pump
P. 334

Technoeconomic performances                                       329

            ii. In heating season with frost formation, cycle operation was assumed to be 15 times/day. In
               heating season without frost formation, the duration of the frosting operation was assumed
               to be 12 h/day.
            iii. When an ASHP unit works at the heating season with frost formation, the system frosting
               COP was assumed at the average value of COP in 60 min, as listed in Item 3 in Table 10.2
               (When it reached 60 min, the COP decreased dramatically).
            iv. When the ASHP unit works at the heating season without frost formation, the system COP
               was assumed at the average value of COP in the first 10 min, as listed in Item 4 in
               Table 10.2.
            v. The COP showed a good linear relationship with the FEC, allowing the values of the COP
               at different FECs to be calculated.
            vi. The total indoor heat supplied showed a good linear relationship with the FEC. The values
               of the indoor heat supplied at different FECs could be calculated.
           Based on the six assumptions and the data listed in Table 10.2, a series of experimental
           results in Case F3 was calculated and summarized in Table 10.10, with its FEC at
           96.6%. Clearly, all the data in Case F3 were much bigger than those in Cases F1
           and F2. The COP and total indoor heat supplied at the different stages listed in
           Table 10.10 would be used in the economic analysis.
           (3) Defrosting assumptions
           To calculate the running cost at the defrosting stage, the following five conditions
           were further assumed:
             i. Defrosting duration showed a good linear relationship with the FEC; thereby, the defrosting
               durations at different FECs could be calculated.
            ii. Total power inputs to the compressor and indoor air fan showed a good linear relationship
               with the FEC, allowing the values of the total power inputs to the compressor and indoor air
               fan at different FECs to be calculated.
            iii. Energy from the indoor air showed a good linear relationship with the FEC, allowing the
               relative values at different FECs to be calculated.
            iv. FEC showed a good linear relationship with the total frost accumulation. Therefore, the
               FECs could be calculated when the total frost accumulated changed.
            v. The frost accumulation difference between Case D2 and Case D4, 31 g, was considered as
               evaporated and neglected.


            Table 10.10 Calculation data and experimental results of the two frosting cases
            Item     Parameters                      Case F1       Case F3

            1        Valves’ status                  Fully open    Evenly adjusted
            2        FEC of outdoor coil             75.7%         96.6%
            3        Average value of COP (60 min)   4.10          4.55
            4        Average value of COP (first 10 min)  4.23     4.58
            5        Indoor heat supplied (60 min)   11,116 kJ     11,719 kJ
            6        Indoor heat supplied (first 10 min)  1922.6 kJ  1950.6 kJ
            7        Conditions shown in Fig. 10.16  (A) and (B)   (C) and (D)
   329   330   331   332   333   334   335   336   337   338   339