Calculation of release rates and extents  11 1


















































                  Fig. 4.3  (Reynolds Number R0.* against pool area)



                  This gives a pool area as follows:

                        A = 5.65 x lo2 a [q(P - 105)]0.5 Ro.2 rp M   m2 (Equation 4.23)

                  The equation for extent of  the hazardous area is again empirical and is:

                       X = 1625 Q/LEL(mixture) x source length]'.'4   m (Equation 4.24)

                  From Equation 4.19 the volume release of  gas is as follows:

                                                        AP
                                      Q~ = 1.64 x  ~o-~A T/RO.*                 m3 /s