Page 100 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 100

Be st Practice 2 .17          Pump Best Practices




















       Fig 2.16.3   Pump minimum flow protection

          Pump discharge temperature rise calculations should be  pumpage systems, where the internals will not be affected by
       performed for all multistage, low specificgravity (lessthan  corrosion or blockage.
       0.8), and low NPSH available applications, in order to de-
       termine if an automatic minimum flow bypass system is
       required.                                            Motor overload protection
          Automatic minimum flow bypass systems can be either  If the motor driver is not sized for horsepower capability at the
       external or internal, but must reliably open at the specified set  end of the operating curve, the motor will trip on motor
       point. All instruments and valves used must be capable of  overload breaker protection unless some means is provided to
       repeatable operation. Failure of a minimum bypass system to  prevent an excess horsepower requirement.
       function when it is needed can cause catastrophic pump  One alternative is to install an orifice to limit flow and therefore
       damage.                                              power requirements. If an orifice is installed, be aware that erosion
          External, minimum flow, bypass systems incorporate an  and/orcorrosionispossible,andrequire inspection at turnarounds.
       external sensing transmitter, controller, conventional two way  Since horsepower is a function of flow and pressure, these
       control valve and flow orifice assembly. An internal, minimum  variables can be limited to prevent motor overload.
       flow, bypass system incorporates all of the above components  Automatic motor overload protection can limit motor amps
       internal to the minimum flow bypass valve. It is recommended  to a preset value by using a controller with input amps to control
       that internal, minimum flow, bypass valves be used only in clean  system level, flow or pressure as required.








         Best Practice 2.17Practice 2.17
         Best
         Install flow switches in manual minimum flow bypass    I have observed that most centrifugal pumps that are subject to
         systems to prevent centrifugal pump damage from recir-  recirculation and/or vaporization are only supplied with manual mini-
         culation and vaporization.                         mum flow control valves which are not instrumented to detect low flow.
           If a pump is supplied with a manual minimum flow control valve, it  Failure to open these valves during low flow conditions subjects the
         should be equipped with a flow switch set to actuate in the control  pump to low MTBFs caused by: bearing failure, mechanical seal failure,
         room at levels which are 10% before the minimum flow value is  impeller and case wear ring seizure.
         reached.                                           Benchmarks
         Lessons Learned                                    This best practice has been used in projects since the 1990s, and has
         The failure to respond immediately to low centrifugal pump  resulted in optimum pump safety and reliability (MTBFs exceeding 80
                                                            months).
         flow results in significant pump damage and exposure to
         safety issues.



       B.P. 2.17. Supporting Material
       Refer to B.P. 2.16 above for reference material.





           74
   95   96   97   98   99   100   101   102   103   104   105